In IEC 61935-1 we see the following text:
6.7 Accuracy performance requirements for Level IV field testers over 600 MHz
The Level IV requirements shall apply to measurements of class FA cabling up to 600 MHz and pass/fail evaluation criteria shall apply. Measurement data over 600 MHz shall be provided for information only. Detailed requirements over 600 MHz are for further study.
Accuracy becomes a real issue above 600 MHz for field testing. At 1,000 MHz, the Insertion Loss accuracy is going to be at least +/- 6 dB. The cabling industry will not accept this level of inaccuracy. At the last IEC 61935-1 meeting, no field test equipment manufacturer came forward with an accuracy proposal above 600 MHz for Permanent Link testing.